108099 Manual motor protective circuit breaker Ex9S32A 0.63A

EAN: 8592765080998

Manual motor protective circuit breakers Ex9S32A provide overload, short-circuit and phase-failure protection for the three-phase asynchronous motors with not frequent starting. They are also suitable for power distribution line protection or can be used simply as an isolator. The right setting of adjustable overload current allows to optimize motor protection by means of circuit breaker. In case of 3P application, correct setting of Ir provides also protection against overload caused due to a phase lost. Ambient temperature compensation function reduces the impact of ambient temperature. Release testing mechanism enables to test the function of the system and control rotary knob lock mechanism prevents illegal operation. Motor protective circuit breakers can be combined with wide range of accessories including auxiliary and signal contacts, shunt trip and undervoltage releases. It is possible to create diverse combination of accessories.

Characteristics

Paremeter Value
Rated operation power at AC-3, 230 V 0.09
Phase failure sensitive YES
With integrated under voltage release NO
Adjustment range undelayed short-circuit release
Rated operation power at AC-3, 400 V 0.18
Rated permanent current Iu 0.63
Depth 98
Degree of protection (IP) IP20
Height 97
Width 45
Type of electrical connection of main circuit Frame clamp
With integrated auxiliary switch NO
Thermal protection YES
Rated short-circuit breaking capacity Icu at 400 V, AC 100
Rated operating voltage
Type of control element Turn button
Device construction Complete device in housing
Number of poles 3
Overload release current setting
Switch off technique Thermomagnetic

Documents

Document Type Document Name Size Format
Manual Mounting instruction Ex9S32 1.6mb PDF
Declaration of Conformity EU Declaration of conformity Ex9S32A 0.5mb PDF
Datasheet Datasheet Ex9S32A 2.2mb PDF
Catalogue Catalogue Industrial Devices 0.0gb PDF WEB